Vacuum Drop Test of Air-Cooled Condensers in Operation


Redacción Científica, 2018
16 Páginas

Extracto

Table of contents

1 Introduction

2 Standard Vacuum Drop Test

3 Leakage Test with ACC in Operation
3.1 Inert Gas Accumulation in ACC during Operation
3.2 Loss of Condensing Capacity Caused by Surface Blanketing
3.3 Effective Pressure Effect

4 Comparison of Static and Steady State Results

5 Conclusion

Glossary

Bibliography

Abstract

Vacuum tightness is critical for air-cooled condensers operating at low absolute pressure. Low vacuum is aimed for because vacuum dominates the power plant efficiency. To verify vacuum tightness usually a vacuum drop test is made with the system empty at normal atmospheric temperature and free of any liquids. This test is done before commissioning of the power unit and generally follows the recommendations of the Heat Exchanger Institute (HEI) as outlined in §6.1.1 of “Standards for Steam Jet Vacuum Systems”.

However, over time of operation the power plant may develop leakages, which were not present at the time of the original drop test. This calls for a tightness test at operating conditions where pre-conditions for the standard vacuum drop test are not fulfilled. The report describes a vacuum drop test without interfering too much into normal power plant operation. The test is suitable for stationary operating conditions using standard operation readings.

The assessment of leakage flow is based on the measured vacuum decay rate. It is shown that vacuum decay rates taken from tests before and after commissioning are different. Contractual fixing of acceptable vacuum decay rates should therefore be treated with care. Example graphs for easy evaluation are given.

Keywords: Air-cooled Condenser; ACC; Air Leakage; Vacuum decay; HEI; VGB-R126L; VGB-R131

1 Introduction

To safeguard stable operation all vacuum systems must be hermetically sealed. Therefore, prior to commissioning of the vacuum system the vacuum tightness is checked [1, 2]. Generally, these tests are made according to the recommendations of the Heat Exchanger Institute, HEI [3]. Air-cooled condensers (“ACC”) are characterized by a huge vacuum volume which is due in the first place to large steam ducts. The condenser bundles constitute only a small fraction of the overall volume. A short description of ACC features is shown in fig. 1 below.

A typical ACC consists of one or more parallel streets with a multitude of heat exchangers arranged in an A-frame geometry at approximately 60° base angle. The condensation is done in two steps with primary and secondary condenser in sequence. The tube bundles are combined in individual heat exchanger modules which are similar in geometry. The set of heat exchangers forming a module is normally served by one fan. Steam supplied via the turbine exhaust duct enters the primary condenser section at the exchanger top manifold and flows down the tubes to the condensate collection line (“CCL”). A considerable fraction of steam is condensed along the flow path through the primary condenser and, at the same time undergoes a pressure drop due to friction. Condensate and residual steam are collected in the CCL which conveys the remaining steam to the secondary condenser section (“dephleg­mator”) and all condensate via the condensate line to the condensate tank. At dephlegmator inlet the remaining steam enters from below and is condensed during up-flow in the exchanger tubes. The secondary condensate is drained back to the CCL by gravity and re-heated to CCL temperature. All inert gases are carried to the dephlegmator outlet along with the steam flow. The dephlegmator exit connects to the inert gas evacuation unit which keeps the vacuum permanent. To suppress extreme condensate sub-cooling the tank may be re-heated via an equalizing line.

illustration not visible in this excerpt

Fig. 1: General ACC

2 Standard Vacuum Drop Test

The standard vacuum drop test procedure used for ACC’s is described in “Standards for Steam Jet Vacuum Systems”, §6.1.1 issued by HEI [3]. The test is done with the ACC out of operation. The ACC is treated as static volume losing its vacuum through leakages which allow influx of ambient air into the system. To perform the test the steam duct inlet must be sealed and the total vacuum volume properly assessed. How­ever, leakages in the vacuum range of the turbine may not be included. The absolute leakage rate is paramount for accurate design of the evacuation unit.

With a test over a short period of time at constant ambient temperature and constant total volume the ideal gas equation of state holds:

illustration not visible in this excerpt

The change of mass per time is same as the inflow of inert gas (or leakage rate)

illustration not visible in this excerpt

with the vacuum decay rate

illustration not visible in this excerpt

Summarizing, [illustration not visible in this excerpt]

This leads for 20°C ambient temperature to the following quantity equation:

illustration not visible in this excerpt

which corresponds to the formula given in §6.1.1 of [3]. Therefore, to estimate the leakage rate at static conditions only vacuum decay rate and total volume are needed. Figure 2 shows example graphs of equation (2) as function of the vacuum decay rate for ambient temperatures in the range of 5°C to 35°C. The lower the ambient temperature the higher the leakage rate.

In practical applications it is common to use the vacuum decay rate as leakage indicator (see fig. 3). This value is based on HEI recommendation of inert gas flow rate in vacuum condensers [4]. The ACC supplier uses these data to properly design the evacuation system capacity. The examples of vacuum decay rate in figure 3 have been calculated as function of the total ACC volume for 20°C ambient temperature. As could be expected, the smaller the ACC volume the higher the vacuum decay rate.

illustration not visible in this excerpt

Fig. 2: Static HEI Leakage Test

illustration not visible in this excerpt

Fig. 3: Static Vacuum Decay Rate, 20°C

3 Leakage Test with ACC in Operation

With the ACC in operation the pre-conditions for using the HEI vacuum test are no longer applicable [3]. Therefore, §3.3.5 of VGB ACC acceptance test standard [1] recommends an air leakage test following VGB Guideline R-126 L (“Recommendations for Design and Operation of Vacuum Pumps for Steam Turbine Condensers”) [5]. However, this test requires a multitude of single measurements and the modification of the vacuum piping by different standardized leakage nozzles. So, normal operation of the ACC is somehow affected during the test. Therefore, at time of erection the HEI test is accepted by clients and suppliers of ACC equipment as confirmation of vacuum tightness in deviation from the VGB test code [1].

None-the-less a situation may arise after commissioning of the power unit to check the vacuum tightness of the system because of loss of vacuum. A leakage test avoiding extra time and effort by using operational data would be extremely desirable. For the proposed simplified method we need to consider at least steady state operation in order to come close to meaningful results.

For the following procedure the steam saturation line is needed. A good approximation is

illustration not visible in this excerpt

or [illustration not visible in this excerpt]

with [illustration not visible in this excerpt]

For the ACC operation decay test the inert gas evacuation is blocked for some time (by closing the evacuation valve), while all operational parameters (steam flow, fan settings, ambient conditions) are kept constant. The loss of vacuum due to inert gas accumulation is visible by the change of turbine exhaust pressure over time. This suggests that the HEI method may apply because again, the ACC volume is filled over time with inert gas. However, accumulation of inert gas impedes also the heat exchange process which has an effect on condensation pressure level as well.

Therefore, we have two sources of vacuum decay during ACC operation:

(a) Inert gas accumulation in ACC,
(b) Loss of condensing capacity caused by blanketing of effective surface,

For simplification we estimate the vacuum decay of each effect separately. The higher value controls the overall pressure increase. The turbine exhaust pressure dominates the thermo­hydraulic state of the ACC and is therefore selected as chief performance parameter. Thus, the effective vacuum decay is

illustration not visible in this excerpt

3.1 Inert Gas Accumulation in ACC during Operation

The inert gas filling of the ACC volume follows the same law as the static volume. Over the test period there will be a small change of temperature. All inerts are quickly heated up to steam temperature. The terminal steam temperature level is crucial for the terminal gas content. As only traces of inerts are contained in the main steam flow the properties of steam will be good enough as approximation for the mixture. Equation (1) therefore turns into[illustration not visible in this excerpt]

This differs from the HEI model (1) by a factor of [illustration not visible in this excerpt] Note that equation (4) takes the form of equation (2) if we exclude condensation and skip to air fill.

3.2 Loss of Condensing Capacity Caused by Surface Blanketing

For the purpose of this investigation the general ACC layout (fig. 1) will be simplified to some extent. The ACC is considered as volume reaching from turbine exhaust to dephlegmator outlet. Steam entering the ACC at turbine exhaust carries all inerts along the flow path to the dephlegmator exit where all steam has been consumed by condensation. Figure 4 shows the simplified system with primary and secondary condenser. The following parameters shall be available from operation records:

- Elapsed time for the test
- Turbine exhaust pressure at begin and end of test
- Condensate temperature, measured at CCL level before tank
- Steam flow rate
- Ambient temperature
- Fan speed settings

Only the first three parameters are of significance as the test will be performed under constant operating condition (flow rate, ambient temperature, fan speed …)

illustration not visible in this excerpt

Fig. 4: Simplified ACC Model

As mentioned, turbine exhaust parameters are pre-dominant for steam flow as well as conden­sa­tion duty. In the range of the ACC vacuum zone three sections may be discerned (see fig. 4): ① initial steam duct supplying steam to the condensers with no condensation, ② bundle range with normal conden­sation comprising primary condenser and initial part of the dephlegmator, and ③ top region of dephlegmator bundles with accumulation of all inert gas (region of surface blanketing).

The most important region is section ③. Initially, all sections are filled with steam and only traces of inert gas. This means that inert partial pressure is so low that steam side temperature and absolute pressure are linked by the steam saturation line. At stop of the evacu­ation the inert gas conveyed with the steam is no longer withdrawn from the dephlegmator outlet and resides there permanently. This goes along with a drop of local temperature which quickly reaches ambient cooling level. The surface blanketed by inert gas-steam mixture is lost for heat trans­fer and does no longer contribute to conden­sation. With constant steam flow under steady state operation the system makes up for the reduction of effective surface by raising the initial temperature difference. This leads to an increase of exhaust steam pressure or, loss of vacuum. Thus, even a small air leakage may result in noticeable increase of system pressure. Over time, the active dephlegmator section in ② is gradually reduced by the blanketed volume. At dephlegmator exit in section ③ we find a steam-air mixture saturated at ambient air temperature.

Vacuum decay caused by loss of cooling can be deduced from the heat balance

illustration not visible in this excerpt

With constant operation parameters the exchanger effectiveness of the active surface is approximately constant as well. Also, the change of condensation heat and steam wetness is small and may be neglected. Thus, we find for active face area

illustration not visible in this excerpt

Steam encounters a pressure drop along the flow path through ducts and tubes which in turn, reduces the local steam temperature (fig. 4). Normally, the temperature change is much smaller on the steam side than on the air side. Consequently, the heat exchange process is close to iso­thermal. Considering duct pressure drop as an abatement of exchanger effectiveness we simply take the turbine exhaust temperature as controlling the initial temperature difference:

illustration not visible in this excerpt

The loss of condensation duty is caused by the blanketed terminal zone of the dephlegmator. Steam and air residing there no longer contribute to heat exchange after being cooled down to ambient level. So, loss of effective surface goes along with formation of an inert gas-steam mixture, so that

illustration not visible in this excerpt

or,[illustration not visible in this excerpt](5)

[...]

Final del extracto de 16 páginas

Detalles

Título
Vacuum Drop Test of Air-Cooled Condensers in Operation
Autor
Año
2018
Páginas
16
No. de catálogo
V421324
ISBN (Ebook)
9783668688254
ISBN (Libro)
9783668688261
Tamaño de fichero
922 KB
Idioma
Inglés
Etiqueta
Air-cooled Condenser; ACC; Air Leakage; Vacuum decay; HEI; VGB-R126L; VGB-R131
Citar trabajo
Dipl.-Ing. Hans Georg Schrey (Autor), 2018, Vacuum Drop Test of Air-Cooled Condensers in Operation, Múnich, GRIN Verlag, https://www.grin.com/document/421324

Comentarios

  • No hay comentarios todavía.
Leer eBook
Título: Vacuum Drop Test of Air-Cooled Condensers in Operation


Cargar textos

Sus trabajos académicos / tesis:

- Publicación como eBook y libro impreso
- Honorarios altos para las ventas
- Totalmente gratuito y con ISBN
- Le llevará solo 5 minutos
- Cada trabajo encuentra lectores

Así es como funciona